Protecta FR Collar Timber Floor Cables

Cable bundles up to 160mm (electrical, data or fibre optic) through a 150mm solid timber or CLT floor. Protecta collar to underside of floor with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/180/180

Products

Details

System ID #: 595
Max Fire Rating: 180
Max Thermal Rating: 180
Size: Cable bundles up to 160mm diam

Build specifications

Add to specification

Downloads

Below are the downloads available. Please tick the ones you would like to receive and complete your details and select how you would like the files delivered to you. Alternatively you can click on the individual download name to view it now.

  Select All
  System diagram
  FC595 Protecta FR Collar Timber Floor Cables Technical Drawing
  Protecta FR Collar AS1530.4 Assessment