Low-noise waste pipes (mineral reinforced PP) and Aquatherm domestic water pipes (PP-R, PP-RP, PP-RCT) 32-160mm through a plasterboard wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Oversize collars permitted. Min wall 100mm. Zero smoke leakage up to 200Pa with 10mm FR Acrylic. Max FRR -/120/120
System ID #: 432
Max Fire Rating: 120
Max Thermal Rating: 120
Size: 32-160mm diam