Conduits up to 40mm of any rigid or flexible plastic, single or bundled, with or without cables up to 21mm (electrical with copper or aluminium conductors, fibre optic or data) in mixed bundles up to 160mm through a 100mm concrete, AAC or masonry wall. Protecta collar both sides, with Protecta FR Acrylic sealant. Zero smoke leakage up to 200Pa. Max FRR -/90/90
System ID #: 613
Max Fire Rating: 90
Max Thermal Rating: 90
Size: Conduits up to 40mm, Bundles up to 160mm