Conduit, flexible or rigid, (PVC, PP or PE, up to 40mm) through a 100mm concrete wall, fully or partially filled with cables (electrical, data or fibre optic) up to 21mm diam. Protecta FR Acrylic 25mm to both sides of wall. Annular space min 10mm, max 30mm. Separation min 30mm between seals. Zero smoke leakage up to 200Pa. Max FRR -/120/120
System ID #: 467
Max Fire Rating: 120
Max Thermal Rating: 120
Size: Conduit up to 40mm diam
Below are the downloads available. Please tick the ones you would like to receive and complete your details and select how you would like the files delivered to you. Alternatively you can click on the individual download name to view it now.