Insulated PVC, PE or PP plastic pipe up to 110mm through a plasterboard or concrete wall 100mm or greater. Insulation interrupted through the wall and may be combustible or non-combustible. Single or double Mulcol Multicollar Slim each side with Mulcol Sealant 10mm deep. Max FFR -/120/120
System ID #: 251
Max Fire Rating: 120 minutes
Max Thermal Rating: 120 minutes
Size: Up to 110mm diameter
Below are the downloads available. Please tick the ones you would like to receive and complete your details and select how you would like the files delivered to you. Alternatively you can click on the individual download name to view it now.