FIRESTOP Duct Wrap-38 Plasterboard Wall Rectangular Duct One-Way Internal Fire

Rectangular duct penetrating a plasterboard wall (1 x 13mm or greater). One-way system. FIRESTOP Duct Wrap-38 (single or double layer) on non-fire side only. Steel angle both sides. Useful for situations where a grease duct opens to the fire source (kitchen). No wrap or collar required from fire source to the first fire-wall. Internal fire only. Up to FRR 120/120/120.

Products

Details

System ID #: 222
Max Fire Rating: 120 minutes
Max Thermal Rating: 120 minutes
Size: Rectangular ducts up to 1800 x 1000mm

System products available for purchase

Buy products

Build specifications

Add to specification

Associated Products & Downloads

Below are the downloads available. Please tick the ones you would like to receive and complete your details and select how you would like the files delivered to you. Alternatively you can click on the individual download name to view it now.

  Select All
  System diagram
  FC222 FIRESTOP Duct Wrap-38 Plasterboard Wall Rectangular Duct One-way System Internal Fire Tech Drawing
  FIRESTOP Duct Wrap-38 Installation Instructions

FIRESTOP Duct Wrap-38
  FIRESTOP Duct Wrap-38 Data Sheet
  FIRESTOP Duct Wrap-38 Installation Instructions
  FIRESTOP Duct Wrap-38 Data Sheet
  FIRESTOP Duct Wrap-38 Video Installation Straps
  FIRESTOP Duct Wrap-38 Video Installation Weld Pins
  FIRESTOP Duct Wrap-38 Video Penetration Details
  FIRESTOP Duct Wrap-38 AS1530.4 Fire Assessment Report AR23108
  FIRESTOP Duct Wrap-38 BRANZ R-value
  FIRESTOP Duct Wrap-38 RIR 23004 (Wall Square Internal 120-60)
  FIRESTOP Duct Wrap-38 RIR 23082 (Wall Rectangular Internal 60-30)
  FIRESTOP Duct Wrap-38 RIR 23083 (Wall Rectangular Internal 60-30)
  FIRESTOP Duct Wrap-38 RIR 23095 (Floor Square Internal 60-15)
  FIRESTOP Duct Wrap-38 RIR 23110 (Wall Circular Internal 60-30)
  FIRESTOP Duct Wrap-38 RIR 24010-1 (Floor Rectangular External 120-120)
  FIRESTOP Duct Wrap-38 RIR 24010-2 (Floor Circular External 120-90)
  FIRESTOP Duct Wrap-38 RIR 24048 (Floor Rectangular Internal 120)

Enter your email address