System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars
Naked Wall

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

AGNI-Shield Pbd or Concrete Wall Copper Pipe

System ID FC825

Copper pipe (up to 150mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Shield extending 150-450mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.

AGNI-Shield Pbd or Concrete Wall Steel Pipe

System ID FC826

Steel pipe (50mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). AGNI-Shield extending 150mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.

AGNI-Shield Pbd or Concrete Wall 42mm Steel Pipe

System ID FC866

Steel pipe (42mm) through a 1 x 13mm plasterboard wall or concrete wall (116mm or greater). Double layer AGNI-Shield extending 50mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.

AGNI-Shield CLT Wall Steel Pipe

System ID FC840

Steel pipe (50mm) through a 100mm CLT wall. AGNI-Shield extending 100mm from each side of wall with AGNI-Seal sealant. Max FRR -/60/60.