System Selector 

The System Selector below will help you choose the correct system. Simply tick the boxes that apply to your situation and click "Search Systems".
You can also use this page to create your own Firestopping Specification. To see how go to Specification Instructions
If you want to restrict your search to a particular product, click your choice from the "Product" dropdown menu. 
If you know the identification number (FCxxx) of the system(s) you want then simply type them into the "System ID" box (separate by commas for multiple numbers) and click "Search Systems".
For an Excel spreadsheet version of all systems, click here for a list of systems

Wall
Floor
Ceiling
Plasterboard
Concrete
CLT
Korok/Speedpanel
Plastic Pipe
PEX Pipe
AluPEX Pipe
Metal Pipe
Copper/Brass Pipe
Cables
Cable Trays
Conduits
Pair Coils
Elect Dist Box
Joints and Gaps
Tilt Slab
Steel
Combos
Ducts
Smoke Seal
Blanks
Hatches
Collars
Naked Wall

Product :
Required Fire Rating :
System ID(s) :
Search Systems    

AGNI-Seal Pbd or Concrete Wall Joints

System ID FC836

Joints in plasterboard (2 x 13mm) or concrete (min 116) walls up to 40mm wide vertical or horizontal. AGNI-Seal to both faces of the wall. Max FRR -/120/120.

AGNI-Seal Concrete Floor Joints

System ID FC834

Joints in concrete floors (min 120mm) from 10mm to 40mm wide. AGNI-Seal to both faces of floor. Max FRR -/180/150.

AGNI-Seal Plasterboard Ceiling Copper Pipe

System ID FC820

Copper pipe (any size up to 100mm) through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.

AGNI-Seal Plasterboard Ceiling Steel Pipe

System ID FC821

Steel pipe (up to 50mm) through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.

AGNI-Seal Plasterboard Ceiling Sprinkler Head & Steel Pipe

System ID FC822

Sprinkler head and steel pipe through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.

AGNI-Seal Plasterboard Ceiling Cables

System ID FC823

Single cables (TPS, Coax or Data, 40mm spacing) through a 1 x 13mm or greater plasterboard ceiling. AGNI-Seal to the depth of the plasterboard. Max FRR -/60/60.

AGNI-Seal Pbd Wall 1x13 Single Cable

System ID FC846

Single cables (Data, Coax, TPS) through one side only of a 1 x 13mm plasterboard wall. Spacing 40mm. AGNI-Seal to the depth of the wall with 10mm cone. Max FRR -/60/60.

AGNI-Seal Pbd Wall 1x13 Data Cable Bundle

System ID FC847

Cable bundle (up to 5 x data cables) through one side only of a 1 x 13mm plasterboard wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.

AGNI-Seal Pbd Wall 1x13 TPS Cable Bundle

System ID FC848

Cable bundle (up to 5 x TPS cables) through one side only of a 1 x 13mm plasterboard wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.

AGNI-Seal Pbd Wall 1x13 Brass Wingback

System ID FC849

Brass Wingback through fire-side only of a 1 x 13mm plasterboard wall. AGNI-Seal to the depth of the wall with 20mm cone. Max FRR -/60/60.

AGNI-Seal CLT Wall Cable Bundle

System ID FC841

Cable bundles (up to 8 x TPS cables) through a 100mm CLT wall. AGNI-Seal to the depth of the wall with 10mm cone each side. Max FRR -/60/60.